Babel Buster BB3-7301 BACnet Router plus Gateway is used to route between BACnet IP and MS/TP, and also includes a Modbus TCP gateway.
Babel Buster BB3-7301 BACnet Router plus Gateway is used to route between BACnet IP and MS/TP, and also includes a Modbus TCP gateway.

Babel Buster BB3-7301 BACnet Router plus Gateway

Your Price: $529.00
Retail Price:$661.00
Your Savings:$132.00(20%)
Part Number:BB3-7301
Control Solutions’ Babel Buster BB3-7301 is a BACnet router, slave proxy, and client/server gateway that allows remapping objects from multiple slaves into one master. You can use the BB3-7301 as just a router, just a client/server, or both at the same time. The BB3-7301 also includes BBMD support. The BB3-7301 is a performance upgrade of Control Solutions’ original BB2-7030 BACnet router.

The BB3-7301 as a BACnet Router will route IP to MS/TP and vice versa via its local ports, and supports full router capability for multi-hop internetworks including via NAT WAN routers. Routing is simple to set up. Routing can be used without any other gateway features enabled.

The BB3-7301 as a BACnet Slave Proxy will provide I-Am responses on behalf of MS/TP devices that do not have I-Am support, or are slave-only devices. The slave proxy capability will allow systems to utilize dynamic address binding with devices that do not support dynamic binding.

The BB3-7301 as a BACnet Client/Server Gateway will poll BACnet IP and/or BACnet MS/TP slaves or servers, and retain copies of selected object properties. Upstream clients may then query the BB3-7301 to receive data originating from multiple devices. When used as a gateway, the BB3-7301's routing can be disabled to avoid conflict with other routers on the network.

The BB3-7301 includes a Modbus TCP client/server that provides optional BACnet to Modbus gateway capability. Value objects will poll their assigned Modbus register at the interval you specify. The content of the Modbus register will be given as the Present Value of the BACnet Value object when read. The Modbus register is written each time the BACnet Value object is written. The Value object corresponds well with the Modbus Holding register.

As a Modbus gateway, Input objects will poll their assigned Modbus register at the interval you specify, and provide the Modbus data as the Present Value when read. Commandable Output objects can be used to write Modbus registers, and will update the Modbus device each time BACnet is updated.

• Universal, fully configurable
• No extra software or drivers to buy

• BACnet IP to MS/TP Router
• Configured or learning, I-Am route learning, I-Am-Router route learning
• Slave proxy to support MS/TP slave-only devices
• Client/Server gateway for remapping BACnet objects
• Read/Write any standard BACnet objects as a Gateway
    • Up to 5,000 objects
    • Analog, Binary, Multi-State object types
    • Input, Output, Value objects
• Commandable BACnet objects implement priority array
• BBMD, COV support
• BB3-7301 is also Modbus TCP client/server
• Bidirectional data exchange between BACnet and Modbus
• Supports Modbus coils, discrete inputs, input registers, holding registers
• Supports signed, unsigned 16-bit, 32-bit, 64-bit integer Modbus registers
• Supports IEEE 754 floating point (32-bit and 64-bit) Modbus registers
• Supports Mod-10 format (2, 3, 4-register)
• Modbus register mapping configured via secure web interface
• Modbus registers may be scaled (x10, x0.1, etc.)
• Modbus (master) polling interval configurable per point
• User defined Modbus register map for Modbus server
• Built-in data scaling for units conversion
• Support for packed holding registers
• Direct import of CSV files for faster point mapping
• Hardened EIA-485 transceiver for BACnet MS/TP
• 10/100BaseT Ethernet for BACnet IP and Modbus TCP
• Configure via secure web pages with password protection
    • TLS 1.2
    • RSA-1024/SHA-256 self-generated certificates
    • Supports externally generated certificates
• Flash file system with XML configuration files
• Field upgradeable firmware
• Includes “10X” file capacity
• Powered by 12-24V DC/AC 50/60 Hz
• Power Consumption: 0.1A @ 24VDC
• DIN rail mounting, 100mm H x 70mm W x 60mm D
• Pluggable screw terminal block for power & RTU network
• Operating temperature -40°C to +85°C
• Humidity 5% to 90% non-condensing
• FCC Class A, CE Mark
• Listed to UL 916 and (Canadian) C22.2 No. 205-M1983