Babel Buster MX-71-SP Proprietary Serial to BACnet IP Gateway is used to connect serial devices to a BACnet IP or Modbus TCP network.
Babel Buster MX-71-SP Proprietary Serial to BACnet IP Gateway is used to connect serial devices to a BACnet IP or Modbus TCP network.

Babel Buster MX-71-SP Proprietary Serial to BACnet IP Gateway

Your Price: $419.00
Retail Price:$524.00
Your Savings:$105.00(20%)
Part Number:MX-71-SP
Babel Buster MX-71 BACnet IP to Modbus Gateway provides a BACnet IP client and server, Modbus TCP client and server, and Modbus RTU port configurable to be master or slave. Most often used to connect Modbus devices to a BACnet IP network, the MX-71 is configured via simple web page templates to read and write Modbus registers in one or more Modbus slaves, making that data accessible as BACnet objects on the BACnet IP network.

The MX-71 includes a BACnet IP client which allows BACnet IP devices to be accessible from Modbus TCP or RTU. You configure the device instance, object type and instance, and poll interval for reading or writing BACnet objects. The object data is stored in the MX-71 server for subsequent retrieval by the remote Modbus client (or master). The same polling schemes that apply to Modbus also apply to remote BACnet IP slaves polled by the MX-71's BACnet IP client.

The MX-71-SP is a special version of the MX-71 that allows one to repurpose the serial communication port to be used for a proprietary serial protocol instead of Modbus RTU. When used for interpreting a proprietary protocol, a Script Basic program would be written to send and receive via the serial port as applicable, and interact with the local BACnet objects under user program control.

The MX-71-SP allows you to BACnet enable enable serial devices that otherwise have no network connection. Combined with rule templates, Script Basic can generate BACnet COV notifications. Script Basic also has access to TCP and UDP connections, and can potentially interpret proprietary IP protocols as well.


MX-71-SP

MX-71-RTU Features

• Universal, fully configurable
• No extra software or drivers to buy

• Connect Proprietary Serial Protocol Devices to BACnet IP
• Script Basic programming for custom serial protocols
• Read/Write any standard Modbus register via BACnet objects
• Up to 5,000 objects
• Analog, Binary, Multi-State object types
• Input, Output, Value objects
• Read/Write any standard BACnet object via Modbus
• Bidirectional communication between BACnet and Modbus
• Supports Modbus coils, discrete inputs, input registers, holding registers
• Supports signed, unsigned 16-bit, 32-bit, 64-bit integer Modbus registers
• Supports IEEE 754 floating point (32-bit and 64-bit) Modbus registers
• Supports Mod-10 format (2, 3, 4-register)
• Modbus register mapping configured via secure web interface
• Modbus registers may be scaled (x10, x0.1, etc.)
• Modbus (master) polling interval configurable per point
• Commandable BACnet objects implement priority array
• Hardened EIA-485 transceiver for Modbus RTU
• 10/100BaseT Ethernet for BACnet IP and Modbus TCP
• Powered by 10-30VDC or 12-24VAC 50/60 Hz
• Power Consumption: 0.1A @ 24VDC
• Panel mount, 70mm H x 131mm W x 38mm D
• Pluggable screw terminal block for power & RTU network
• Operating temperature -40°C to +85°C
• FCC Class A, CE Mark



Accessories

24VDC Wall Plug Power Supply