You are currently visiting our e-Commerce site. Full documentation, user guides, data sheets, videos,
and more as applicable by product, may be found at www.csimn.com.

 

VP3-2290-AG Remote Telemetry Unit, GPS, AT&T 4G LTE
Model VP3-2290 Global Remote Telemetry Unit is ideal for demanding remote alarm monitoring and data logging. It includes 4G LTE cellular data modem, 20 inputs, 2 outputs, Modbus RTU and J1939.

VP3-2290-AG Remote Telemetry Unit, GPS, AT&T 4G LTE

Your Price: $1,569.00
Retail Price:$1,961.00
Your Savings:$392.00(20%)
Part Number:VP3-2290-AG

Choose Options

Temp Range help

Control Solutions’ i.Report Model VP3-2290-AG Global Remote Telemetry Unit is ideal for demanding remote alarm monitoring and data logging. It includes an AT&T 4G LTE Cat 3 cellular data modem built in. The VP3-2290-AG also includes GPS built in for tracking applications. The i.Report VP3-2290 logs periodic data to the LogMyData Cloud and also sends alarm notices to the cloud. Apps running on the cloud then distribute notifications to the appropriate recipients via SMS text message, email, and/or voice call. (See also VP3-2290-V, VP3-2290-VG, VP3-2290-A)

The VP3-2290 includes 12 hardwired sensor inputs, which are universally configurable as analog, temperature (thermistor), or discrete/dry contact inputs. Two of the analog inputs have 30V input range for directly monitoring batteries. The VP3-2290 includes 8 discrete inputs selectable for active voltage sense or dry contact closure to ground. The VP3-2290 also includes 2 discrete outputs for functions such as generator start on command or local alarm indicator.

The VP3-2290 includes a Modbus RTU port which may operate in master or slave mode. The VP3-2290 may poll multiple Modbus slaves to greatly expand I/O capability. The VP3-2290 may also operate as a slave allowing a PLC in a larger system to write data to the VP3-2290.

The VP3-2290 also includes a CAN/J1939 port for applications such as engine monitoring. The VP3-2290 can receive any standard J1939 message, including transport protocol. The VP3-2290 can initiate data read requests. The VP3-2290 can transmit J1939 messages sending data provided by the web portal or derived internally. Message construction is completely configurable, and transport protocol is supported in both directions.

The VP3-2290 supports report by exception for alarm monitoring. Periodic data logging will occur at the rate desired, but alarms and warnings will be called in immediately. The web portal will then dispatch any number of emails, SMS text messages, and voice calls as desired.

Control Solutions’ i.Report Cellular Global Remote Telemetry Unit, Model VP3-2290-AG, offers an array of advanced features:

• Remote monitoring and data logging
• Tracks 400 data points with dual alarm thresholds per point
• Supports trending and report-on-delta for all 400 points
• Cellular connectivity using 4G LTE
• GPS tracking and geo-fencing for mobile apps
• Battery backed real time clock
• Programmable soft PLC included
• Modbus RTU master/slave port
• CAN 2.0b/J1939 communication port
• Engine monitoring functions assigned to any data object
• Over the air control
• Over the air firmware update
• 12 Universal inputs
- - - 0-10VDC, thermistor, dry contact
- - - 0-30VDC range on 2 channels
- - - 4-20mA with external resistor
- - - 16-bit sigma-delta converter
- - - Continuously self calibrating
• 8 Fixed discrete inputs, 0-30VDC input range
- - - Voltage sense or dry contact closure to ground
- - - Hardware pulse counter on 2 channels
• 2 Discrete outputs, 30VDC 1A open drain FET
• Internal temperature sensor
• Hardened RS-485 serial port (Modbus RTU)
• USB port (connects to laptop for service)
• 32-bit ARM7 processor, 512K Flash
• 128K EEPROM for configuration storage
• Operates from 10-30VDC or 12-24VAC
• DIN rail mounting, 100mm H x 105mm W x 60mm D
• Operating temperature 0°C to +70°C
• Operating range -30°C to +70°C optional

Delivery: Typically 1-3 weeks.